IFRM 12X9103 10235296
Technical data
general data
- mounting type
-
- non-flush
- nominal sensing distance Sn
-
- 4 mm
- approvals/certificates
-
- ATEX 1G
Подробно описание
electrical data
- switching frequency
-
- < 2 kHz
- normal operating voltage
-
- 8,2 VDC
- voltage supply range +Vs
-
- 5 … 30 VDC
- current consumption undamped
-
- > 4 mA
- current consumption damped
-
- < 1 mA
- current consumption max. (no load)
-
- 10 mA
- output circuit
-
- NAMUR
- residual ripple
-
- < 10 % Vs
mechanical data
- type
-
- cylindrical threaded
- housing material
-
- brass nickel plated
- dimension
-
- 12 mm
- housing length
-
- 34 mm
- connection types
-
- cable, 2 m
safe maximum values
- EC-type-examination Certificate
-
- PTB 03 ATEX 2146
- marking
-
- II 1G Ex ia IIC T6 Ga
- current Ii
-
- < 37 mA
- voltage Ui
-
- < 13,5 VDC
- power Pi
-
- < 0,125 W
- internal capacitance Ci
-
- < 50 nF
- internal inductance Li
-
- < 0,2 mH
- operating temperature Ta (temp. class T5)
-
- -20 … +60 °C
- operating temperature Ta (temp. class T6)
-
- -20 … +40 °C
ambient conditions
- operating temperature
-
- -25 … +75 °C
- protection class
-
- IP 67